Auxiliary Converter — Real Circuit & Technical Data (BUR)

Electrical Engineering Electric Locos Chapter 14/28 16 min read Source: Verified Source
हिन्दी में पढ़ें

Create a free account to track your reading, save important notes and practise this topic.

Each locomotive carries 2 real boxes enclosing the static auxiliary converter system: BOX1 (containing BUR1) and BOX2 (containing BUR2, BUR3, and the battery charger — the charger is fed from one of the two converters and may be considered a functional part of the converter system). Three auxiliary converters connect to the main transformer's auxiliary-services winding; each is rated 100 kVA output with short-circuit-proof 3-phase output at 415V. BUR1/BUR2 give variable output frequency (0-50Hz); BUR3 gives fixed 50Hz output.

The battery charger is supplied from BUR3; if BUR3 has a fault, BUR2 feeds the battery charger instead. Rated output approx. 111V, the charger charges the loco batteries and supplies low-voltage loads — its low-voltage output is electrically insulated from both the input and the 3-phase output. Converters use external forced-convection cooling (approx. 5 m/sec); internal thermostats run the fans once temperature exceeds 50°C, until it drops below 35°C. Both boxes and the 3-phase output chokes mount in the machine room; the intermediate chokes are built into the main transformer tank itself, for convenience and weight saving.

Real Technical Data — Full Ratings

SectionParameterReal Value
InputSupply voltage1000V AC +200V/−300V
InputApparent power100 kVA
InputCurrent (rms)150A (at 100kVA, 700V)
InputFrequency50Hz ± 3%
InputRated insulation voltage1200V
InputTest voltage (50Hz/60 sec)4250V
Intermediate circuitVoltage550 VDC
Intermediate circuitRated current155 ADC
Intermediate circuitShort-term overload190 ADC
Intermediate circuitRated insulation voltage (capacitor)900V
Intermediate circuitTest voltage (50Hz/60 sec)2600V
Output — ACRated voltage (fundamental rms)415V
Output — DCDC voltage111V
Output — ACRated frequency (BUR1&2 / BUR3)50Hz / 50Hz
Output — ACRated current (incl. battery charger)140A
Output — DCMax. battery-charger current (battery only)80A
Output — DCMax. battery-charger current (user + battery)110A
Output — AC/DCNo. of poles (conductors)3 / 3
Output — AC/DCRated insulation voltage900V / 150V
Output — AC/DCTest voltage (50Hz/60 sec)2600V / 1500V
Control unitSupply voltage (operating range)77...137.5V
Control unitPower consumption120W
ThermalLosses at rated power, Box12 kW
ThermalLosses at rated power, Box25 kW
ThermalVentilator supply voltage36...56V
ThermalVentilator power losses5W
ThermalAir rate5 m/sec

Real Circuit Description & Main Parts

Main converter parts: a half-controlled rectifier bridge, an intermediate filter (inductor + capacitor), three inverter legs connected as a 3-phase inverter, an electronic control unit, a 3-phase output inductor, and the battery charger (a 3-phase transformer + rectifier). Other components detect actual values needed to control the process and maintain reliable power-electronics operation.

Real Protective & Measurement Devices

4 Real Protective Devices
  • Battery charger circuit breaker [100]: protects against overload by magnetic tripping, isolating the charger from inverter output on internal short-circuit — the converter needn't switch off and the loco can keep running until battery capacity is exhausted.
  • Input fuse [40]: protects from serious consequential damage from power-component failure in the rectifier bridge or regulation/monitoring defects.
  • Surge arresters [40.1]: protect rectifier-bridge [50.11] semiconductors from over-voltage spikes.
  • Damping filter RC [49.2/49.1]: a small filter limiting the rate of rise of voltage spikes, avoiding spurious thyristor firing.

Auxiliary Converter Control Unit — Real Rack Contents

The control unit handles all control and electronic-protection functions, communicating with the vehicle control unit (FLG) via the MVB optical bus.