Auxiliary Transformer — Types, Working Principle & Full Specifications

Electrical Engineering Traction Distribution Chapter 44/87 20 min read Source: Official
हिन्दी में पढ़ें

Create a free account to track your reading, save important notes and practise this topic.

Auxiliary Transformers in electrified sections are required for colour light signal equipment (signal lights), switching stations, and traction sub-stations. The Auxiliary Transformer provides 25kV/240V, 50Hz single-phase supply for cabins, sub-stations, feeding and switching posts, stations, block-huts, RRIs, and level crossings with gate signals. It is a static device working as a step-down transformer, transforming power from one AC circuit to another at the SAME frequency — the circuits are conductively disjointed but magnetically coupled by a common time-varying magnetic field.

Working Principle

Based on electromagnetic induction: (a) when a conductor cuts magnetic flux (or flux cuts the conductor), an EMF is induced; (b) the magnitude of this EMF is proportional to the rate of change of flux. When the primary winding connects to AC mains, current flows and — since this winding links with an iron core — produces alternating flux that also links the secondary winding, inducing an EMF there at the SAME frequency as the supply. This induced secondary EMF delivers current to an external load. The core's flux also links the primary winding itself, producing a self-induced EMF that OPPOSES the applied voltage — known as 'back EMF' — which limits primary current, analogous to how back EMF in a DC motor limits armature current.

Connection (Tap)Tap No.Primary VoltageSecondary VoltageRatio (%)
5-4126250 V240 V109.375 / 105%
4-6225000 V240 V104.166 / 100%
6-3323700 V240 V98.75 / 95%
3-7422500 V240 V93.75 / 90%
🎯
Exam Focus — The 4-Tap Table Is a Real, Complete, Worked Answer
This tap table matches exactly the RDSO tapping range already known — '105% to 90% of primary voltage in steps of 5%' — but now with the ACTUAL voltage figures attached: 26250V (105%), 25000V (100%, the nominal tap), 23700V (95%), 22500V (90%). Notice the connections aren't in a simple sequential order (5-4, 4-6, 6-3, 3-7) — this reflects the real physical tap-changer switch layout, not a logical voltage sequence, which is worth remembering if a question shows a tap-changer diagram.

Technical Data — All Four Capacity Ratings

Parameter5 kVA10 kVA25 kVA100 kVA
Primary rated current0.2 A0.4 A1.0 A4.0 A
Secondary rated current21 A42 A105 A416.66 A
Primary voltage25 kV25 kVNormal 25kV (Min 19kV, Max 27.5kV)25 kV
No load loss50 W60 W60 W60 W
Load loss at 75°C200 W300 W300 W300 W
Impedance voltage at rated current, 75°C5%5%5%5.19%
Mass of core & winding—80 kg220 kg360 kg
Mass of oil—98 kg—275 kg
Total mass—300 kg515 kg880 kg
Volume of oil—110 litres—310 litres

All four ratings SHARE the following common specifications: Type — double-wound, single-phase, oil-immersed, natural-air-cooled (ONAN), step-down, for outdoor installation. Secondary voltage: 240V. Rated frequency: 50Hz ±3%. Insulation level: primary lightning impulse withstand 190kV peak, primary short-duration power-frequency withstand 70kV rms (secondary 3kV rms), primary induced over-voltage 80kV rms. Tapings: off-circuit tap changer, +5% to -10% in steps of 5%, all taps carry full load current continuously. Polarity: Subtractive. Temperature rise limits: winding 50°C (resistance method), oil 40°C (thermometer), current-carrying parts in air 40°C, hot spot NOT to exceed 115°C — all over a 45°C ambient. Type of cooling: ONAN. Insulation class: 'A' for all windings. Current density (max): 2.5 A/mm² for both windings. Minimum creepage distance: 900mm for 36kV class, 90mm for 3.6kV class.

🎯
Exam Focus — 5 kVA Is the Odd One Out on Losses
The 10/25/100 kVA ratings all share IDENTICAL no-load loss (60W) and load loss (300W) figures despite their very different power ratings — only the 5kVA rating differs, with lower losses of 50W/200W. This is genuinely counter-intuitive (you might expect losses to scale up steadily with kVA rating across all four), so the 5kVA-is-different pattern is worth anchoring specifically.

Construction — The 11 Parts & Components

The Auxiliary Transformer consists of: HV winding and LV winding (electrically separated but magnetically coupled), wound on a common magnetic core. One end of the primary connects to the 25kV system through a bushing; the other end connects to the tank (earth) through a bushing and link. Both secondary terminals mount on the tank through bushings — one used as PHASE, the other EARTHED and used as NEUTRAL. Windings and core are immersed in insulating oil in the tank.

Bushing Test VoltagePrimary (36kV class)Secondary (3.6kV class)
Highest test voltage for equipment36 kV rms3.6 kV rms
Rated short-duration wet power-frequency withstand70 kV rms10 kV rms
Rated lightning impulse withstand190 kV peak40 kV peak
Minimum creepage distance900 mm90 mm