Traction transformers are deliberately designed to handle short bursts of overload beyond their rated capacity — real, standardised figures govern exactly how much and for how long, since exceeding these limits risks permanent insulation damage.
Overload Rating — Real Figures
- Overload rating: 50% overload for 15 minutes, OR 100% overload for 5 minutes — after the transformer has attained steady temperature during continuous operation at full load.
- Maximum permissible temperature rise over a 45°C ambient: Winding 50°C (measured by resistance method), Oil 40°C (by thermometer), Current-carrying parts 35°C (by thermometer).
- The hot-spot temperature after either 50% overload for 15 min OR 100% overload for 5 min must NOT exceed 100°C for a 45°C ambient temperature.
- Interval between two successive overloads (after continuous working at maximum 45°C ambient) is 3 HOURS — applying identically to both the 50%/15min and 100%/5min overload types.
Tap Setting — Real Procedure
Traction transformers usually have OFF-LOAD tap changers (operated locally or by remote control), with taps ranging from +10% to (-)15% in steps of 5%. To decide the correct tap setting, a recording voltmeter is connected at the traction substation to the secondary side of a Potential Transformer, tracking the voltage variation pattern over 24 hours, across at least 3 TYPICAL days.
Since any change in grid inter-connections affects traction substation voltage, SSE(PSI) must keep in touch with Supply Authorities regarding system changes — arranging a fresh 24-hour voltage-reading cycle and re-adjusting the tap setting if needed whenever such a change occurs.