रखरखाव अनुसूची — मासिक, त्रैमासिक, अर्ध-वार्षिक, वार्षिक
| मासिक — मद | अवलोकन/मानक |
|---|---|
| Visual inspection of transformer | Any sign of oil leakage, overheating |
| Clean externally (conservator, bushing, tank) | By clean cotton cloth |
| Silica gel & oil condition in breather cup | Reactivate/replace if pink; top up oil in cup if less |
| HT and LT bushing terminal connections | Tighten if loosen |
| Oil level in conservator | Top up with new oil of 60kV BDV, up to mark |
| D.O. fuse and assembly | Visually check overheating, connections |
| AT enclosure and vegetation | Clean, remove vegetation |
| Pole-mounted ICDP switch and fuses | Check overheating of lugs, proper fuse rating, loose connections — fuse wire 20 SWG for 34A, 22 SWG for 24A |
| Caution board and anti-climbing device | Availability and condition |
| त्रैमासिक — मद (अतिरिक्त) | अवलोकन/मानक |
|---|---|
| D.O. fuse barrel and fuse element | Breakage, overheating — use proper size fuse element |
| Arcing horn gap for HV bushing | Split horn gap maintain 82.5mm MINIMUM |
| Foundation condition | Any crack or damage |
| Structure bond and earth connection | Tightness |
| Unusual sound of equipment | Should be soundless |
| अर्ध-वार्षिक — मद (अतिरिक्त) | अवलोकन/मानक |
|---|---|
| BDV of oil | Minimum 30kV (with 2.5mm gap) |
| IR — HV to Earth | 200 MΩ minimum (2.5kV megger) |
| IR — HV to LV | 200 MΩ minimum (2.5kV megger) |
| IR — LV to Earth | 2 MΩ minimum (500V megger) |
| Secondary voltage on each tap (no-load, full-load) | Within permissible limit |
| Earth resistance and connections | Not more than 10 ohms |
| वार्षिक — मद (अतिरिक्त) | अवलोकन/मानक |
|---|---|
| Winding continuity on all tappings | By multimeter |
| Tap changer smooth operation | No obstruction |
| DGA of oil and Polarization Index | Gases within permissible limit; time index = 600 sec / 60 sec |
| Acidity of transformer oil | Maximum 0.5 mg KOH/gm |
| Ratio test (AC to HV, measure LV) | Measure the voltage |
| Painting | If required |
| HT and LT jumper connections | Flash mark, loose connection, overheating |
आवधिक ओवरहॉल (POH)
परीक्षा पर ध्यान — 7 से 10 वर्ष, अन्य स्रोतों से आंकड़े की पुष्टि
ओवरहॉलिंग या तो ट्रांसफार्मर दोषपूर्ण होने पर, या 7 से 10 वर्ष की सेवा के अंत में किया जाता है।
ओवरहॉलिंग (POH) रिपेयर शॉप में या व्यापार के माध्यम से किया जा सकता है।
- पहले सामान्य सफाई: टैंक, रेडिएटर, HV एवं LV बुशिंग के आसपास जितना संभव हो उतनी गंदगी हटाएं।
- खोलने से पहले, डिस्कनेक्ट करें: तेल निकालें, सभी लीड डिस्कनेक्ट करें।
- खोलने के बाद: वाइंडिंग IR मापें; किसी भी दरार हेतु सभी कोर समर्थन बोल्ट जांचें।
- कार्य विवरण: नए फिल्टर किए गए तेल से वाइंडिंग/कोर साफ करें।
- फिटिंग निरीक्षण: सिलिका जेल श्वासयंत्र को उथले पैन में 150-200°C पर 2-3 घंटे गर्म करके पुनः सक्रिय किया जाता है।
- असेंबली के बाद परीक्षण: मेगरिंग, निरंतरता परीक्षण, अनुपात परीक्षण, विभिन्न टैप पर वोल्टेज आउटपुट।
- अंतिम जांच: किसी भी बिंदु/कपलिंग/जोड़ से तेल रिसाव की जांच करें।
सहायक ट्रांसफार्मर जीवन को प्रभावित करने वाले कारक
- नमी: अत्यधिक अवांछनीय — तेल के डाइइलेक्ट्रिक गुणों तथा पेपर इन्सुलेशन दोनों को प्रभावित करती है।
- ऑक्सीजन: सेल्युलोज इन्सुलेशन के साथ प्रतिक्रिया करती है एवं उसे विघटित करती है।
- ठोस अशुद्धियां: डाइइलेक्ट्रिक शक्ति को काफी कम करती हैं — उपाय समय-समय पर छानना है।
- वार्निश: कुछ का ऑक्सीडाइज़िंग प्रभाव होता है।
- वाइंडिंग की ढीलापन: सेवा के कुछ महीनों बाद, ट्रांसफार्मर कॉइल स्वाभाविक रूप से बैठ सकते हैं।
ट्रांसफार्मर तेल — परीक्षण मानक
सहायक ट्रांसफार्मर IS:335 के अनुसार इंसुलेटिंग तेल के साथ पूर्ण आपूर्ति किए जाते हैं।
| परीक्षण | अनुमेय (IS:1866) | पुनः स्थिति में लाया जाए | बदला जाए |
|---|---|---|---|
| Electric strength (BDV) below 72.5kV | Min. 30 kV | Less than specified value | If min. value not attained after reconditioning |
| Specific resistance (Resistivity), Ω/cm at 27°C | Above 10×10¹² | Between 1×10¹² to 10×10¹² | Below 1×10¹² |
| Water content, below 145kV | Max. 35 ppm | Greater than specified | — |
| Dielectric dissipation factor, Tan Delta at 90°C | 0.01 or less | Above 0.01 to 0.1 | Above 0.1 |
| Neutralization value, mg KOH/g of oil | 0.5 or less | Above 0.5 | Above 1.0 |
| Interfacial tension, N/m at 27°C | 0.02 or more | 0.015-0.02 | Below 0.015 |
| Flash point, °C | 140 or more | 125-140 | Below 125 |
| Sludge | Non-detectable | Sediment | Perceptible sludge |
परीक्षा पर ध्यान — नए-तेल फैक्ट्री विनिर्देश जानबूझकर इन-सर्विस अनुमेय मानों से सख्त हैं
इस अध्याय में दो तालिकाओं को भ्रमित न करें — यह इन-सर्विस तेल की तीन-स्तरीय कार्रवाई सीमाएं दिखाती है।
| निर्माता के कारखाने में नया तेल (IS:335) — विशेषता | आवश्यकता |
|---|---|
| Electric strength — new unfiltered oil | Min. 30kV rms |
| Electric strength — after filtration (RDSO requirement) | 60kV rms |
| Resistivity at 90°C / 27°C | Min. 35×10¹² / 1500×10¹² Ω-cm |
| Dielectric dissipation factor (Tan Delta) at 90°C | Max. 0.002 |
| Water content | Max. 50 ppm |
| Interfacial tension at 27°C | Min. 0.04 N/m |
| Flash point | Min. 140°C |
| Dissolved gas content | 4-8% |
| Neutralization value — total acidity | Max. 0.03 mg KOH/g |
| Neutralization value — inorganic acidity/alkalinity | Nil |
तेल शुद्धिकरण: उद्देश्य सभी संदूषकों को हटाना है — संरक्षित सबसे महत्वपूर्ण गुणवत्ता डाइइलेक्ट्रिक शक्ति है।
- तेल नमूना सावधानियां: IS:6855-1973 के अनुसार साफ, सूखी, एम्बर ग्लास बोतलों का उपयोग करें।
- नमूना प्रक्रिया: ड्रेन-कॉक संदूषण को समाप्त करने हेतु पहले कम से कम 1 लीटर निकालें।
सामान्य विफलताएं एवं उपचार
- तेल रिसाव — स्थान-विशिष्ट कारण: स्क्रू जोड़, गास्केट जोड़, वेल्ड जोड़, कपलिंग, ड्रेन प्लग।
- निम्न BDV — कारण: निष्क्रिय (गुलाबी) सिलिका जेल से नमी संदूषण।
- बुशिंग विफलता — HV फ्लैशओवर: बिजली डिस्चार्ज/अति-वोल्टेज, अपर्याप्त आर्किंग हॉर्न गैप।
- वाइंडिंग विफलता: ओवरलोड शॉर्ट सर्किट से प्राथमिक लीड खुला/अर्थेड।
- अत्यधिक अति-तापन: आंतरिक दोष से तापमान वृद्धि।
- निम्न IR मान: तेल में नमी।
- भिनभिनाहट की आवाज़: ढीला कोर।
स्थिति निगरानी एवं DGA दोष निदान (अनुपात विधि)
तीन रखरखाव दृष्टिकोण मौजूद हैं: नियमित, आवधिक, एवं स्थिति-आधारित निगरानी।
| गैस अनुपात स्थिति | इंगित दोष |
|---|---|
| Methane/Hydrogen = 1 | Slight overheating, below 150°C |
| Methane/Hydrogen = 1 AND Ethane/Methane = 1 | Overheating between 150-200°C |
| Ethane/Methane = 1 | Overheating between 200-300°C |
| Ethylene/Ethane = 1 | Normal conductor overheating |
| Methane/Hydrogen = 1 AND Ethylene/Ethane = 1 | Circulating currents and overheated joints |
| Acetylene/Ethylene = 1 | Flashover without power flow current |
| Ethane/Methane = 1 AND Acetylene/Ethylene = 1 | Tap changer selector breaking current |
| Ethylene/Ethane = 1 AND Acetylene/Ethylene = 1 | Arc with power flow through, or persistent arcing |
अनुपात-कोडिंग परंपरा: 1.0 से कम अनुपात 0 नामित किए जाते हैं; 1.0 से अधिक अनुपात 1 नामित किए जाते हैं।
| गैस | < 4 वर्ष सेवा में (ppm) | 4-10 वर्ष (ppm) | > 10 वर्ष (ppm) |
|---|---|---|---|
| H₂ (Hydrogen) | 100-150 | 200-300 | 200-300 |
| CO₂ (Carbon dioxide) | 3000-3500 | 4000-5000 | 9000-12000 |
| CO (Carbon monoxide) | 200-300 | 400-500 | 600-700 |
| CH₄ (Methane) | 50-70 | 100-150 | 200-300 |
| C₂H₆ (Ethane) | 100-150 | 150-200 | 200-400 |
| C₂H₄ (Ethylene) | 30-50 | 100-150 | 800-1000 |
| C₂H₂ (Acetylene) | 20-30 | 30-50 | 150-200 |
| दोष प्रकार | H₂ | CH₄ | C₂H₆ | C₂H₄ | C₂H₂ | CO₂ |
|---|---|---|---|---|---|---|
| Arcing | 500-1000 | 20-130 | 10-30 | 10-30 | 40-100 | 3000-4000 |
| Partial Discharge | 500-1000 | 20-130 | 10-30 | 10-30 | 10-15 | 3000-4000 |
| Hot Spot | 20-150 | 10-30 | 10-30 | 150-200 | 10-15 | 3000-4000 |
| Gradual Overheating | 20-150 | 10-30 | 150-200 | 10-30 | 10-30 | 3000-4000 |
परीक्षा पर ध्यान — एसिटिलीन एवं एथिलीन द्वारा आर्किंग को हॉट स्पॉट से अलग करें
आर्किंग एवं पार्शियल डिस्चार्ज एसिटिलीन (C₂H₂) को छोड़कर लगभग समान दिखते हैं: आर्किंग = 40-100 ppm, पार्शियल डिस्चार्ज = केवल 10-15 ppm।
क्या करें एवं क्या न करें
- करें: नियमित रूप से DO फ्यूज बदलें; केवल RDSO-अनुमोदित ट्रांसफार्मर तेल आपूर्तिकर्ताओं का उपयोग करें।
- न करें: अनलोडिंग हेतु कम-क्षमता वाली पुली/टिरफोर का उपयोग करें; ढीले कनेक्शन छोड़ें।
परीक्षा पर ध्यान — 250g सिलिका जेल न्यूनतम एक सटीक, आसानी से परीक्षण योग्य संख्या है
अधिकतर गुणात्मक 'करें' सूची के बीच, 'न्यूनतम 250 ग्राम सिलिका जेल श्वासयंत्र क्षमता' एक सटीक, परीक्षण योग्य संख्या है।