This chapter is an extract of a real, independent RDSO Specification (No. ETL/PSL/65(8/84)) — distinct from the main chapters covered earlier in this subject. It gives a clean, itemised consolidated list of protective relays, genuinely useful as a memorisation checklist since it summarises what earlier chapters covered individually in depth.
Where Relays Physically Sit
For protection of transformer, substation, and feeder, all relays are provided on a control panel housed in the MASONRY CUBICLE at the traction sub-station (TSS) — a real, specific physical detail about relay housing.
(i) Transformer Protection — The Real 5-Item List
- Differential relays.
- IDMT (Inverse Definite Minimum Time) over-current relays — for BOTH primary (HV) and secondary (LV) sides. The HV-side IDMT relay ALSO carries an instantaneous over-current element.
- Instantaneous Earth Leakage relays — on BOTH primary (HV) and secondary (LV) sides.
- High-speed Inter-Tripping relays.
- Auxiliary relays for transformer faults — namely Buchholz, Excessive Winding and Oil Temperature trip/alarm, and Low Oil Level alarm.
(ii) Overhead Equipment Protection — The Real 5-Item List
- Admittance-type DIRECTIONAL Distance Protection relays — the same Mho relay covered earlier, described here with the added technical term 'admittance-type' and 'directional.'
- Admittance-type relay for protection against Wrong Phase Coupling.
- Instantaneous Over-Current Relays.
- Panto Flashover Relay.
- Delta-I relay for high-resistance fault.
Auto-Reclosing & Inter-Tripping — Real Confirming Detail
This RDSO extract adds a specific real detail not as explicitly stated in the earlier chapter: the auto-reclosing feature helps CHECK/RESTRICT the continuance of arc specifically as a moving locomotive's pantograph passes the overlap opposite the feeding post — and this specifically protects the OHE CATENARY from consequent damage, naming the catenary specifically as what's being protected, not just 'OHE' generically.