Real Fault MVA & Current by Voltage Class
| Item | 66kV | 110kV | 132kV | 220kV |
|---|---|---|---|---|
| Max Fault MVA | 3500 | 5000 | 5000 | 10000 |
| Fault Current | 30.62 kA | 26.24 kA | 21.86 kA | 26.24 kA |
| Rated Breaker Breaking Current | 31.5 kA | 31.5 kA | 25 kA | 31.5 kA |
Real Worked Example — 220kV Substation, Single Transformer
For a 220kV incoming bus (fault level 10,000 MVA) feeding a 20 MVA, 220/25kV power transformer, primary-side fault current = Fault MVA ÷ (√3 × Volt in kV) = 10,000 ÷ (√3 × 220) = 26.24 kA.
Using the per-unit reactance method: system reactance up to the 220kV busbar (at 100 MVA assumed base) = (Chosen base MVA × 100) ÷ Fault Level = (100 × 100) ÷ 10,000 = 1%. Transformer reactance at 100 MVA base (assuming 20 MVA transformer's short-circuit impedance is 12%) = (100 × 12) ÷ 20 = 60%. Total reactance = 1% + 60% = 61%.
Fault level on the 25kV bus, just opposite the substation = (100 × 100) ÷ 61 = 163.93 MVA. Fault current there = 163.93 ÷ 25 = 6.557 kA — dramatically LOWER than the 220kV-side fault current, since the transformer's own impedance genuinely limits fault current on the downstream side.
Two Transformers in Parallel — Real Effect on Fault Level
This explains a genuinely important real-world observation: though the fault current with two parallel transformers is still less than the breaker's rated capability, the breaker's ASSIGNED rating is deliberately higher than the calculated fault current, because IEC/IS/BS standards mandate a fixed series of standard breaking-current ratings rather than custom-matching each installation's exact calculated figure.
Standardised Breaking Current Series (IEC/IS/BS)
Co-ordination Table — Real Voltage/Current Combinations
| Rated Voltage (kV) | Rated Short Circuit Breaking Current (kA) | Normal Rated Current (Amps) |
|---|---|---|
| 72.5 | 12.5 | 800 / 1250 |
| 72.5 | 16 | 800 / 1250 |
| 72.5 | 20 | 1250 / 1600 / 2000 |
| 72.5 | 31.5 | 1250 / 1600 / 2000 |
| 123 | 12.5 | 800 / 1250 |
| 123 | 20 | 1250 / 1600 / 2000 |
| 123 | 25 | 1250 / 1600 / 2000 |
| 123 | 40 | 1600 / 2000 |
| 145 | 12.5 | 800 / 1250 |
| 145 | 20 | 1250 / 1600 / 2000 |
| 145 | 25 | 1250 / 1600 / 2000 |
| 145 | 31.5 | 1250 / 1600 / 2000 |
| 145 | 40 | 1600 / 2000 |
| 145 | 50 | 2000 |