OHE Technical Fundamentals

Electrical Engineering Traction Distribution Chapter 3/87 14 min read Source: Verified Source
हिन्दी में पढ़ें

Create a free account to track your reading, save important notes and practise this topic.

French National Railways (SNCF) demonstrated in 1955 that 25kV single-phase, 50Hz AC traction was superior to other systems. Indian Railways adopted it in 1957 in collaboration with SNCF, and now conducts electrification independently. India's first electric train ran BINA to KATNI (Central Railway) on 16.1.1995, on 2×25kV AC traction.

Electrification Progress — Real Historical Data

YearCumulative Electrified (RKM)
1951388
1961748
19713,706
19815,345
19919,968
200114,856
201119,607
201829,228
201934,319
🎯
Exam Focus — 2018-19 Was a Record Year
5,276 RKM was commissioned in 2018-19 alone — the highest ever electrification in a single year, 29% higher than the previous year. By March 2019, 34,319 RKM (50.91% of the total 67,415 RKM network) was electrified, carrying 65.4% of freight and 56.2% of passenger traffic while consuming only 33.2% of total traction fuel cost — a real efficiency argument worth remembering.

Catenary & Contact Wire — Real Specifications

Span, Masts & Portals

Presag, Stagger & Overlap

🎯
Exam Focus — Electrical Clearances
Minimum electrical clearance between live and earthed parts, under worst-case temperature/wind conditions: vertical distance 250mm for long duration / 200mm for short duration; horizontal distance also 250mm for long duration / 200mm for short duration — the same pair of figures applies to both vertical and horizontal, a detail worth noting since it's easy to assume they'd differ.

Anticreep & Section Insulators

In regulated OHE, an anticreep point is installed at the midpoint of the tension length to ensure uniform distribution of mechanical tension along the conductor. Section Insulators separate the OHE of one track from another (e.g. at turnouts/crossovers) and separate secondary tracks/sidings from the main line. When a pantograph crosses from one track's OHE to another's, the overlap between runners prevents sparking during the changeover. Solid core porcelain insulators support the OHE as bracket/stay-arm insulators; 9-ton insulators are used specifically for termination points.