Three Real Types of Clearance
- Phase clearance — the distance between live parts of different potential, to prevent flashovers.
- Earth clearance — the distance between live parts and earthed material.
- Safety clearance (also called sectional clearance) — the minimum distance between an unscreened live conductor and the limits of a work section, required for personnel safety during inspection, operation, and maintenance.
Minimum electrical clearances for outdoor switchgear are stipulated in IS 3072. The full table specifies clearance by voltage rating — but critically, some figures in the table are UNDERLINED, meaning THOSE specific figures (not the alternative ones alongside them) are what RDSO has actually adopted in its own specifications.
Real RDSO-Adopted Clearances (IS 3072)
| Voltage Rating (kV rms) | Impulse Withstand Level (kV peak) | Min Clearance to Earth (mm) | Min Clearance Between Phases (mm) | Min Safety Clearance (mm) |
|---|---|---|---|---|
| 72.5 | 350 | 675 | 810 | 3270 |
| 123 | 550 | 1150 | 1350 | 3750 |
| 145 | 650 | 1380 | 1600 | 3980 |
| 245 | 1050 | 2300 | 2700 | 4900 |
Earthing — Why It Matters
The primary need of earthing is that during a fault, sufficient current flows through the fault path to operate protective gear, while preventing dangerous potential rise on non-live equipment parts. Earthing must have sufficient cross-section and low resistance to provide a path for traction current, provides the RETURN path for traction current, keeps non-current-carrying parts (equipment frames, fencing, structures) at ground potential even after insulation failure, and helps reduce induced-voltage effects in adjacent communication circuits — directly connecting to the induction-effect content covered in the earlier Safety Precautions on Electrified Sections chapter.
Two Real Types of Earthing
- Equipment Earthing — for safety of operating personnel, public, and property. All non-current-carrying metallic parts (circuit breaker frames, interruptor frames, transformer frames, PT/CT frames, steel structures, fencing panels/uprights) connect to the main earthing bus (earth grid) via TWO SEPARATE AND DIRECT connectors.
- System Earthing — one leg of the secondary bushing on the 25kV side of each traction power transformer is solidly earthed to the earthing ring using two 75mm×8mm or 80mm×12mm M.S. flats. The earthing ring is further connected to a buried rail beside the track using four 75mm×8mm M.S. flats (for a two-track section). One designated terminal of each PT/CT/auxiliary supply transformer secondary is also connected to the earthing ring using duplicate 50mm×6mm M.S. flats.
Earth Resistance Limits — The Real Numbers
| Installation Type | Max Combined Earth Resistance |
|---|---|
| Traction Sub-station | 0.5 ohms |
| Switching Station | 2.0 ohms |
| Booster Transformer Station | 2.0 ohms |
| Auxiliary Supply Transformer Station | 10.0 ohms |