Under 25kV AC 50Hz single-phase traction, heavy induction occurs on ALL metallic structures and conductors in the tract — a genuine hazard often overlooked by staff more used to DC traction, where this danger doesn't exist. Induction is two-fold: electro-static (from the high 25kV potential) and electro-magnetic (proportional to the current flowing sub-station-to-loco-and-back, partly via track, partly via earth).
Earthing against induction must be done individually by each working party, as close to the work-spot as possible — the distance between the two earths must never exceed 1 km. Large parallel metallic structures (fencing, platform steelwork) and private-party metallic conductors (clotheslines, power lines) running close to electrified tracks are also subject to dangerous induction and need suitable earthing or public awareness.
Steam Locomotive Working in Electrified Sections
- No steam locomotive may stand with its chimney under an OHE insulator — stabling with chimneys under traction structure is prohibited entirely.
- Continuous blowing of safety valves, sudden blower opening, and priming through exhaust steam must be avoided — all can cause insulator flashover. Sudden engine starting risks wheel slip, which risks priming, which risks flashover — a real cause-and-effect chain.
- Staff must never stand on the boiler shell or tender when stabled under live OHE — risk of electrocution.
- Firing tools must never be lifted or raised towards the OHE, and must always be returned to their position after use. Spraying coal with water under overhead lines is forbidden.
- A hose jet must never be directed at the OHE — only horizontally, well away from it, never vertically.
- Coal/fuel loading only in yards outside electrified zones; coal height in the tender limited to 4.28m above rail level (BG) / 3.65m (MG).
- Regardless of contact-wire height, no one should climb onto the tender to open the water-tank cover or insert the water-column funnel.
Water-Column Safety Interlocking
Watering of steam locomotives under OHE is only permitted within a defined 'watering section' bounded by danger limit boards hanging from the catenary at each end. Each watering section has its own dedicated neutral section (about 12m long, bounded by section insulators) at both ends — specifically to add protection against any locomotive approaching or power 'feeding in' from the live sections beyond.