This chapter covers a genuinely important conceptual insight that ties together the fault-current calculation and breaker-rating content from the previous chapters: WHY the deciding factor for breaker selection is completely different on the primary side versus the secondary side of a traction substation.
Real Standardised Current Series
- Rated short circuit breaking current (kA): 6.0, 8.0, 10.0, 12.5, 16.0, 20.0, 25.0, 31.5, 40.0, 50.0, 63.0, 80.0, and 100 kA.
- Rated normal current (Amps): 400, 630, 800, 1250, 1600, 2000, 2500, 3150, and 4000 A.
The Real 20 MVA Example — A Genuine Eye-Opener
The normal rated current of a 20 MVA transformer's primary winding, for a 132kV system, is only 151.5 Amps. Since these transformers are designed to deliver 100% overload for 5 minutes (the real overload rating from the earlier Transformer Overload Capacity chapter), primary current could reach up to 303 Amps at most. Yet the ASSIGNED normal rated current for the HV circuit breaker across the 66kV/110kV/132kV/220kV systems is 1250 Amps — roughly 4-8 TIMES the actual maximum expected current.
Real Technical Particulars — 220kV vs 25kV Breakers
| Particular | 220kV (Primary) | 25kV (Secondary) |
|---|---|---|
| No. of poles | 2 or 3 as required | 1 |
| Nominal system voltage | 220 kV | 25 kV |
| Highest system voltage | 245 kV | 52 kV class |
| Rated 1-minute power frequency withstand voltage | 460 kV (rms) | 105 kV |
| Rated impulse (1.2/50 µs) withstand voltage | 1050 kV (peak) | 250 kV (peak) |
| Rated normal current | 1250 A | 1600 A |