220kV/25kV Breaker Technical Particulars — Completed
| Particular | 220kV | 25kV |
|---|---|---|
| Rated short circuit breaking current | 31.5 kA | 20 kA |
| Rated breaking capacity (Two Pole) | 7717.5 MVA | 450 MVA |
| Rated breaking capacity (Three Pole) | 13366.7 MVA | — |
| Rated making current | 78.8 kA | 50 kA |
| Rated operating sequence | 0-0.3sec, CO-3sec-CO | 0-0.3sec, 30sec-CO |
| Total breaking time | Not more than 80 ms | Not more than 65 ms |
| Rated short-time withstand current | 31.5 kA for 1 second | 20 kA for 3 seconds |
25kV Interruptors — Real Specifications
Interruptors are provided at feeding posts and switching stations. Most interruptors are NOT required to clear faults — the ONE exception is the interruptor at the sectioning post, called a bridging interruptor, which IS called upon to clear faults under extended-feed conditions (directly matching the emergency-feed extension role covered in the earlier Substation Layout chapter).
Isolating Switches
To guard against mistakes while working on sub-station equipment, safety demands an apparatus that makes a VISIBLE break in the circuit — this is the isolating switch (isolator), also called an off-load switch since it opens/closes only when negligible or no current flows.
- Primary (HV) side isolators: 2-pole or 3-pole. Constructionally divided into: (i) three-post, centre-post rotating double-break type, and (ii) two-post single-break type.
- Primary-side isolators are HORIZONTAL break type; secondary (25kV) side isolators are VERTICAL break type — a real, testable orientation distinction between the two voltage levels.
- Rated normal current of isolators is fixed to MATCH the rated current of circuit breakers and busbars — following the same IEC/IS standardised series covered in the earlier Breaker Selection Criteria chapter.
Current & Potential Transformers
Bushing-type CTs are provided on BOTH primary and secondary sides of traction transformers, exclusively meant for DIFFERENTIAL PROTECTION — directly connecting to the differential relay content covered in the earlier Transformer Protective Devices chapter (spill current from imperfect CT-secondary balance being one of the real mal-operation causes). Separately-mounted 132kV and 25kV CTs, plus 25kV PTs, are of conventional type.