Interruptors, Isolating Switches & CT/PT

Electrical Engineering Traction Distribution Chapter 51/87 13 min read Source: Verified Source
हिन्दी में पढ़ें

Create a free account to track your reading, save important notes and practise this topic.

220kV/25kV Breaker Technical Particulars — Completed

Particular220kV25kV
Rated short circuit breaking current31.5 kA20 kA
Rated breaking capacity (Two Pole)7717.5 MVA450 MVA
Rated breaking capacity (Three Pole)13366.7 MVA—
Rated making current78.8 kA50 kA
Rated operating sequence0-0.3sec, CO-3sec-CO0-0.3sec, 30sec-CO
Total breaking timeNot more than 80 msNot more than 65 ms
Rated short-time withstand current31.5 kA for 1 second20 kA for 3 seconds
🎯
Exam Focus — 25kV Breaks FASTER Despite Being Lower Voltage
A genuinely counter-intuitive real detail: the 25kV breaker's total breaking time (65 ms max) is actually FASTER than the 220kV breaker's (80 ms max) — matching the earlier finding that 25kV also carries a higher rated normal current (1600A vs 1250A). Both facts reflect the same underlying reality: the lower-voltage secondary side handles closer-to-the-load conditions where speed and current capacity matter more directly.

25kV Interruptors — Real Specifications

Interruptors are provided at feeding posts and switching stations. Most interruptors are NOT required to clear faults — the ONE exception is the interruptor at the sectioning post, called a bridging interruptor, which IS called upon to clear faults under extended-feed conditions (directly matching the emergency-feed extension role covered in the earlier Substation Layout chapter).

🎯
Exam Focus — Old vs New RDSO Interruptor Specs
The bridging interruptor's ORIGINAL breaking capacity was specified as 4000 Amps at 27.5kV recovery voltage, with a short-time current withstand capacity of 4000 Amps for 3 seconds. With higher-rating traction transformers now in use, RDSO's NEW specification has increased this to 8kA breaking capacity and 800 Amps normal rated current — a real, quantified upgrade worth distinguishing from the older figures.

Isolating Switches

To guard against mistakes while working on sub-station equipment, safety demands an apparatus that makes a VISIBLE break in the circuit — this is the isolating switch (isolator), also called an off-load switch since it opens/closes only when negligible or no current flows.

Current & Potential Transformers

Bushing-type CTs are provided on BOTH primary and secondary sides of traction transformers, exclusively meant for DIFFERENTIAL PROTECTION — directly connecting to the differential relay content covered in the earlier Transformer Protective Devices chapter (spill current from imperfect CT-secondary balance being one of the real mal-operation causes). Separately-mounted 132kV and 25kV CTs, plus 25kV PTs, are of conventional type.