OHE Inspection Car — Annual Maintenance Checks

Electrical Engineering Traction Distribution Chapter 15/87 16 min read Source: Verified Source
हिन्दी में पढ़ें

Create a free account to track your reading, save important notes and practise this topic.

The OHE Inspection Car carries out a distinct, annual round of highly specific geometric checks at locations that carry disproportionate risk if maladjusted — turnouts/crossovers, section insulator assemblies, overlaps, overline structures, and splices. Points and crossings in particular receive special attention because mal-adjustment of OHE at these locations can lead directly to pantograph entanglement.

7.1 Maintenance of Turnout / Crossover

ParameterStandard Value
Height of contact wire towards turnout, at/near obligatory structureTurnout contact wire = Main line height (H) + 50mm
Turnout span (max)54 m
Pantograph clearance from turnout/crossover wire while on main lineH + 50mm
Stagger of contact wire at obligatory structure — main line200mm max
Stagger of contact wire at obligatory structure — turnout300mm max
Movement of tower wagon from main line to turnout / turnout to main line (take-off/take-on)650mm to 720mm from centre line of pantograph
Vertical distance, register-arm axis to contact plane — with drop bracket300mm
Vertical distance, register-arm axis to contact plane — with steady arm clamp250mm
Stagger of section insulator of turnout/crossover±100mm
Track separation at section insulator — runners towards centre of turnout1.65 m min
Track separation at section insulator — runners away from centre of turnout1.45 m min
Setting distance (implantation) of obligatory structure3.0 m min
Distance of 'G' jumper from obligatory structure5.6 m
Length of 'G' jumper4.0 m
Track separation at obligatory structure150 to 700 mm

7.2 Maintenance of Section Insulator Assemblies

ParameterStandard Value
Clearance, runner to runner460 mm max
Clearance, contact wire to runner230 mm
Encumbrance at section insulatorNot less than 450 mm
Stagger of section insulatorZero

7.3 Maintenance of Overlap OHE and RRA Clamp

ParameterStandard Value
Distance between parallel contact wires — Un-Insulated Overlap (UIOL)200 mm
Distance between parallel contact wires — Insulated Overlap (IOL)500 mm
Stagger of in-running contact wire — tangent track±200 mm
Stagger of in-running contact wire — curved track±300 mm
Overlapping of contact wire2 to 9 m
Number of PG clamps required in 'G' jumper8 (minimum)
🎯
Exam Focus — The Memorable Mnemonic Line
A Hindi field mnemonic is worth remembering as a quick recall trigger for this exact rule: 'JAHAN MILE DO TENSION LENGTH, WAHAN HO G JUMPER WITH DOUBLE (PG CLAMP) STRENGTH' — wherever two tension lengths meet (i.e. an overlap), the G jumper needs double PG-clamp strength. This anchors the '8 PG clamps minimum in the G jumper' rule.

7.4 Annual Maintenance of Overline Structure/Tunnels and Clearances Under Overline Structure

7.5 Splices

7.6 General Annual Maintenance of OHE by Inspection Car

🎯
Exam Focus — UIOL vs IOL, and the Overlap Range
A frequently-confused pair: Un-Insulated Overlap (UIOL) parallel wire spacing = 200mm, Insulated Overlap (IOL) = 500mm — insulated needs more than double the spacing, since it must maintain electrical clearance between the two separately-fed sections, not just mechanical clearance. The overlap length itself (2 to 9m) is a range, not a fixed figure — don't confuse it with the parallel-wire spacing numbers above.