Bus Bars & Lightning Arresters

Electrical Engineering Traction Distribution Chapter 52/87 14 min read Source: Verified Source
हिन्दी में पढ़ें

Create a free account to track your reading, save important notes and practise this topic.

Bus Bars — Strung vs Rigid Type

Two types of busbar are used at traction substations: STRUNG type on the HV side, and RIGID type on the LV (25kV) side.

🎯
Exam Focus — The Real Conductor Upgrade Story
Earlier electrification schemes used All-Aluminium 'spider' conductor (size 19/3, 99mm) for the strung bus, adequate only for fault currents above 17kA. As grid fault levels rose beyond 25kA, this became inadequate — ongoing schemes now use 'Zebra' ACSR conductor (size 61/3.18, dia 28.62mm), capable of withstanding fault currents up to 31.5kA. The strung bus tension is kept between 500-900 kgf, and minimum conductor/jumper diameter must be at least 28mm for a 220kV system (to keep corona losses within limits).

Similarly, the rigid bus in earlier schemes was Aluminium Alloy of 36mm O.D. (36/28mm), capable of carrying 960 Amps normal rated current. With 20 MVA transformers now common, the required rated current increased to 1500 Amps (for short duration), so rigid busbar size increased to 50mm O.D. (50/39mm), capable of carrying 1530 Amps CONTINUOUS current. The rigid bus is supported on insulators at intervals not exceeding 3m, and the minimum height of the 25kV busbar is kept at 3800mm.

💡
Memory Aid — Rigid Bus Is Costlier but More Reliable
Plainly stated: chances of rigid bus failure are very remote, but its installation is costlier than the strung bus — a genuine real-world cost-vs-reliability trade-off, which is exactly why rigid bus is reserved for the 25kV side (fewer, more critical connections) rather than used throughout.

Lightning Arresters — Real Selection & Types

Lightning arresters (also called surge diverters) protect against over-voltages from lightning strokes and switching surges by absorbing energy. An ideal arrester draws negligible current at operating voltage (very high impedance) but negligible impedance during actual surge current flow. LA breakdown voltage must be kept much LOWER than other substation equipment — but not so low that normal supply-voltage variation or switching surges cause a power-frequency flashover.

🎯
Exam Focus — Zinc Oxide Gapless Is the Real Modern Standard
Zinc oxide gapless LAs are the new generation, with 8 real advantages over older types: matching/controlled protective level, faster response (from eliminating the series gap), reduced over-voltages (energy is absorbed), light/rugged construction, improved thermal characteristics, better performance under polluted conditions, better pressure-relief performance, and better sealing. That's genuinely 8 distinct, listable advantages — a real exam could ask for any subset.

Real Installation Rules