Condition-Based Maintenance — CB, CT, Surge Arrester & Relay Testing Instruments

Electrical Engineering Traction Distribution Chapter 58/87 20 min read Source: Official
हिन्दी में पढ़ें

Create a free account to track your reading, save important notes and practise this topic.

Circuit Breakers/Interrupters — Why Monitor These Parameters

Dynamic Contact Resistance Measurement (DCRM) Meter

ChannelConfigurationRangeAccuracy
Contact status24: 4 main + 4 PIR per pole, 3 poles simultaneouslyMeasurement duration 1mS to 40s at 1kC±0.05% ±1 digit
Auxiliary contacts4: 2 dry, 2 wet (expandable to 12+12)24-250V DC±0.05% ±1 digit
Coil current3: Trip/Close coil current1, 2, 5, 10, 25 A DC±0.5% ±1 digit (12-bit)
Voltage (travel characteristics)30-5V DC±0.5% ±1 digit (12-bit)
DCRM channels1/2/3/6: resistance & test current1000, 2000, 4000, 8000 µΩ±1% ±1 digit (12-bit)

Contact Resistance Meter

Time Interval Meter

Current Transformer (CT) Testing — Why Monitor

Current Transformer Excitation, Ratio & Polarity Tester

Current Transformer Burden Ammeter

A rugged, portable field-test instrument specifically checking for: short-circuited secondary turns; short-circuited primary turns; short-circuited secondary wiring; high-resistance connection in the secondary circuit; grounding of secondary winding when mounted on grounded structure; and grounding of a normally-ungrounded wire.

Ammeter Range (A)Burden (ohms)Burden Rating (VA at nominal 5A)
1.250.256.25
2.50.512.5
—125
—250
104100

Designed so the CT secondary under test will NOT be accidentally opened. Uses make-before-break construction for the ammeter range/burden selector switch. Burdens are normally shorted out but can be put in series with the ammeter via a spring-loaded momentary switch.

Surge Arrester — Leakage Current Meter

Surge arrester failure mainly stems from moisture ingress inside the arrester and/or ageing of the oxide blocks — causing severe damage to the arrester pole and neighbouring equipment. Monitoring leakage current measures the Third Harmonic Resistive Component (THRC), providing quick, reliable health information at an incipient stage.

Relay Testing — Primary vs Secondary Current Injection

Test TypeWhat It TestsKey Characteristic
Primary Current InjectionThe WHOLE protective system — CTs, conductors, connection points, relay, circuit breakerRequires breaking the primary circuit; injects a high test current enough to cause the protection equipment to operate; essential when commissioning NEW protection systems or after major repair/component replacement — detects incorrect CT polarity or wrong relay sequencing in differential systems
Secondary Current InjectionOnly the protective RELAY's operation — does NOT test CTs or the overall systemNo need to break the primary circuit; requires LESS current through the operating coil; easier and quicker to set up
🎯
Exam Focus — Primary Injection Is the More Complete but More Disruptive Test
The core trade-off: Primary Injection tests EVERYTHING in the chain (CT through breaker) but requires breaking the primary circuit — appropriate for commissioning or after major repairs. Secondary Injection skips the CT entirely, testing only the relay, but is much easier and faster since the primary circuit stays intact — appropriate for routine relay checks. If a question describes 'verifying CT polarity or detecting wrong relay sequencing in a differential system,' that's specifically a Primary Injection Test capability that Secondary Injection cannot provide.