Thermo Vision Camera imaging is a genuine predictive-maintenance technique: it identifies developing defects on OHE/PSI/RC/station traction equipment by analysing RELATIVE temperature between similar sub-components — not absolute/ambient temperature — allowing rectification before an in-service failure occurs.

Imaging Technique — Real Requirements

Priority Classification — The Real Temperature-Difference Table

Temperature Variation (vs adjacent/similar component)Time to Attend
> 20°C24 hours
10°C – 20°C5 days
5°C – 10°C10 days
< 5°CNormal (routine)
🎯
Exam Focus — 5°C Is the Real Filtering Threshold
Records are filtered on the basis of a 5°C or greater temperature difference — this is the real practical cutoff below which a finding isn't even flagged for prioritised attention (it falls into the 'Normal' category). Defective PG clamps, catenary wire, and jumpers get priority attention regardless of exact classification.

Any defect requiring immediate attention must be reported to the Depot-In-Charge, TPC, and Officer-In-Charge — with immediate rectification ensured, not just logged for later. After rectification, images of the fixed component must also be taken, closing the loop on the record.

OLIVIR-G Plus — Spark Detection System

OLIVIR-G plus assists Overhead Equipment spark detection using a video camera mounted on a locomotive. A GPS receiver tracks the loco's current position, matching it against previously-collected track feature data — this dramatically simplifies identifying exactly WHERE a spark occurred, not just that one occurred.

The accompanying Olivir Mate RT Software identifies sparks in real time, saving them as location-tagged images while a continuous video file also records to a hard drive — these images can later be analysed to recognise the exact type of spark and its precise location.

What Thermo Vision Camera Must Check on 25kV AC OHE

  1. All types of jumpers and their PG clamps.
  2. Catenary splices, 'U' clamps, and bulldog clamps.
  3. Contact splices.
  4. Isolator contacts, connectors, jumpers, and their PG clamps.
  5. Feeder wire jumpers connected with OHE and their PG clamps.

Schedule: the depot/OHE in-charge (SE/JE) should inspect his entire section by thermal imaging once a year, and should cover any OHE Ghat section specifically once every six months (ghat sections — steep gradient sections — get double the frequency given their higher failure consequence).

OLIVIR-G — Real Test Procedure & Flash-Intensity Priority Table

Flash Intensity (Mega Pixel units)Time to Attend
More than 100 units (High Intensity)Within a week
Between 60-100 units (Medium Intensity)Within a fortnight
Between 40-60 units (Low Intensity)Within a month

Schedule: the current collection test should be carried out over the entire section by ADEE (TRD) level every two months. Sr.DEE/TRD will cover the entire section once in six months.

🎯
Exam Focus — Two Different Metrics, Don't Confuse Them
Thermo Vision Camera measures TEMPERATURE DIFFERENCE in °C (>20°C=24hrs, 10-20°C=5days, 5-10°C=10days, <5°C=normal — see the table above in this chapter). OLIVIR-G measures FLASH/SPARK INTENSITY in Mega Pixel units (>100=within a week, 60-100=within a fortnight, 40-60=within a month) — a completely different physical quantity for a completely different failure mode (sparking/current collection vs. resistive heating). Also note the different inspecting authorities and periodicities: Thermo Vision is SE/JE-level, annual (6-monthly for ghats); OLIVIR-G is ADEE-level, bi-monthly (6-monthly for Sr.DEE).