Lightning Arrester — Maintenance, Failure Modes & LCM III Condition Monitoring

Electrical Engineering Traction Distribution Chapter 55/87 20 min read Source: Official
हिन्दी में पढ़ें

Create a free account to track your reading, save important notes and practise this topic.

Maintenance Schedule

Yearly TestStandard Value
IR value of each LA unit (2.5/5kV megger) — for 42kV LAMore than 1 GΩ
IR value of each LA unit — for LA on HV sideMore than 10 GΩ
Earth resistance of earth connectionNot more than 0.5 Ω

Yearly records for each LA must include: location, rating, make, serial no., date of manufacture, date of commissioning, date of measurement, IR value, THRC value of leakage current, total leakage current, number of surges passed, and remarks.

🎯
Exam Focus — The LA IR Value Is 10x Higher on the HV Side
For a 42kV LA, the yearly IR threshold is >1 GΩ, but for LA on the HV side it's >10 GΩ — a clean 10x ratio, similar in shape to the Surge Arrester LV/HV split covered in the PSI equipment chapter (which used a >1000 MΩ / >10,000 MΩ pair — also a 10x ratio, though these are DIFFERENT documents/contexts, so don't assume the exact figures are identical, just that the 10x pattern recurs).

Pre-Monsoon Check: before monsoon onset, ensure no scheduled maintenance is overdue for LA. Additionally ensure: proper cleaning of all arresters; IR value of each unit POSITIVELY checked (to avoid bursting/failure); all connections tight; leakage current monitor reading checked (if provided); surge counter reading checked (if provided).

Failure, Causes & Remedial Action — 5 Real Documented Failure Modes

From a seminar on LA maintenance (23rd-24th August), the following common failures were documented, each with a genuine root cause and a real, escalating remedial procedure.

FailureCause
Low insulation resistance valueIngress of moisture inside LA; ageing of zinc oxide blocks
LA burst or puncturedHeavy rain and thundering
Hair cracks on porcelain portionHitting by foreign body; manufacturing defect
Hot spot on top connectorLoose connection
Top diaphragm burstManufacturing defect

The general remedial pattern across all 5 failure modes: (1) disconnect and unload the LA from line carefully; (2) if the LA is a single unit, check IR of a spare unit — if within permissible limit, replace the defective LA entirely; (3) if the LA has multiple units, identify and remove just the defective unit, replacing it with a healthy unit of the SAME MAKE (never mix makes); (4) check IR of the fully re-assembled LA — must be within/more than permissible limit; (5) re-erect, re-take IR value, reconnect all connections, and commission. The 'Hot Spot on Top Connector' failure has an extra first-response step before this pattern: if the connection is merely loose, simply TIGHTEN it and replace overheated nuts/bolts — only escalate to unit replacement if the connector plate is badly overheated/damaged beyond simple repair.

DOs and DON'Ts

Condition Monitoring by LCM III

In normal service, a metal oxide surge arrester (MOSA) carries a continuous but small leakage current, typically 0.1-2 mA — dominated by a CAPACITIVE component, with the RESISTIVE component only 5-25% of the capacitive one. MOSAs normally operate at a continuous voltage of 60-80% of rated voltage. Because ZnO's non-linear characteristic makes even a large increase in resistive leakage current (Ir) barely noticeable within the total leakage current, measuring the 3rd harmonic resistive component specifically — via LCM III — is the best way to obtain sensitive, reliable information about arrester health without any shutdown.

🎯
Exam Focus — The Official THRC Action Thresholds
Per RDSO TI directorate maintenance instruction RDSO/TI/MI/0041 (Rev-1) dated 08.04.2010: ONE COMPLETE CYCLE of LA leakage-current measurement must be completed PRIOR TO monsoon onset every year. Arresters with resistive leakage current between 350-500 µA should be CLOSELY MONITORED; beyond 500 µA, the arrester should be REPLACED and jointly checked with the manufacturer. These exact figures also appear in the PSI equipment chapter's Surge Arrester THRC table — confirming this is one consistent, official rule cited consistently across multiple sources, not a one-off number.

LCM III — Principle & Five Named Accessories

Principle: the non-linear resistance of ZnO blocks introduces a 3rd harmonic resistive component in the leakage current when stressed by a sinusoidal voltage — this component best indicates changes in the arrester's non-linear characteristics over time. Since harmonic content in the operating voltage itself also increases harmonic content in the leakage current, the measurement must COMPENSATE for system-voltage harmonics, or an apparent increase in resistive current could be a false signal rather than a genuinely faulty arrester.

How to Use LCM III — 4-Step Procedure

  1. Connect the LCT across the earthing strip of the LA, to measure total leakage current.
  2. Place the DAP, using the THS, at the base of the LA — to pick up system-voltage harmonics, giving the capacitive current component.
  3. Connect the SCU with leads from the LCT and DAP, to determine the resistive component of leakage current.
  4. Connect the SCU and SPU — leakage-current waveforms of the various components can be viewed directly in the SPU without an external oscilloscope.

Measured Parameters (5 Display Fields)

FieldMeaning
It (mA)Peak value of TOTAL leakage current
Ic (mA)Peak value of the CAPACITIVE current
I3t (mA)Third-order harmonic current measured
Ir (mA)Resistive current of the LA — UNCORRECTED value, must be corrected for voltage/temperature variations
Ir (corr)CORRECTED resistive current, referenced to 70% rated voltage and 20°C
🎯
Exam Focus — Ir vs Ir(corr) Is the Exact Point to Test
A precise, easy-to-test distinction: Ir is the RAW measured resistive current, still contaminated by whatever the actual voltage/temperature happened to be at measurement time. Ir(corr) is the number actually used for meaningful comparison over time — normalized to a fixed reference point (70% rated voltage, 20°C) so that measurements taken on different days, under different conditions, can be validly compared against each other.

LCM applications: as a portable instrument for regular condition checks; to monitor an arrester over a shorter/longer period (e.g. investigating unexpectedly high leakage current in more detail); or permanently installed for continuous registration at substations of major importance. Recommendation: the first resistive-leakage-current measurement should be taken shortly AFTER installation, as the best reference 'fingerprint' for all future comparisons. Ageing typically causes a GRADUAL increase in leakage current over time — establishing regular measurement procedures allows detecting aged arresters and removing them from service BEFORE failure.