Earth Leakage Protection — Real Settings
Back-up protection for internal earth faults uses sensitive, high-speed earth leakage relays, provided SEPARATELY for primary and secondary sides, each connected to a separately-mounted CT. These relays are adjustable between 20% and 40% of 5A in equal 5% steps, and must be T-10 class with operating time NOT exceeding 10 ms.
Over-Current Protection — Real Settings Table
| Relay Position | Current Setting | Time Multiplier Setting |
|---|---|---|
| IDMT overcurrent — primary side | 80% to 320% | 0 to 3 secs |
| Instantaneous overcurrent — primary side | 400% to 1600% | — |
| IDMT overcurrent — secondary side | 80% to 320% | 0 to 3 secs |
Inter-Tripping — The Real Lockout Mechanism
Differential relays and earth leakage relays (both sides) PLUS over-current relays (primary side) all cause inter-tripping of BOTH the 132/110/66kV and 25kV circuit breakers associated with the transformer. This inter-tripping also fires on Buchholz trip. The secondary-side IDMT overcurrent relay, however, trips ONLY the 25kV-side breaker — a genuinely narrower scope than the other relays.
Other Protective Devices — Wiring Detail
The transformer, as supplied by the manufacturer, comes fitted with 4 real warning/protective devices: low oil level alarm, Buchholz relay with alarm/trip contact, oil temperature indicator with alarm/trip contact, and winding temperature indicator with alarm/trip contact. These contacts wire up to a WEATHER-PROOF terminal box mounted on the transformer BY THE MANUFACTURER — the connection is then extended to the alarm/trip circuit and the annunciator on the control board.
25kV OHE Protection — The Real 8-Function Requirement List
The protection scheme for 25kV overhead equipment must genuinely fulfil ALL of these 8 real functions:
- Detect ALL short circuits over the zone of overhead equipment fed by the feeder circuit breaker.
- Operate with MINIMUM delay in opening the circuit breakers.
- Refrain from operating at maximum working current — DISCRIMINATE between max load current and short circuit current, even though load current can sometimes exceed short-circuit current in magnitude, especially when the fault is remote from the substation.
- Detect and isolate faults on OHE caused by accidental coupling of two different phases from an adjacent substation.
- Provide single-shot auto-reclosing of the feeder circuit breaker after a PRESET TIME INTERVAL adjustable between 0.5 SECONDS and 30 SECONDS — a genuinely wide, specific real range not stated this precisely in earlier chapters.
- Reclose the 25kV feeder circuit breaker via single-shot automatic reclosing when it trips on fault through ANY of the three relays: Mho (wrong phase coupling) relay, and instantaneous over-current relay.
- Detect and isolate flashover caused by a pantograph on an overlap in front of the traction substation when the panto moves from live to dead section over the insulated overlap — provided by the Panto Flashover Relay.
- Detect and isolate a HIGH-RESISTANCE OHE ground fault — a fault type explicitly noted as one that CANNOT be [caught by the standard relays alone, requiring the Delta-I relay covered in the earlier chapter].