Static Type Relays — Real Manufacturer Specifications

Electrical Engineering Traction Distribution Chapter 36/87 15 min read Source: Verified Source
हिन्दी में पढ़ें

Create a free account to track your reading, save important notes and practise this topic.

Indian Railways has been using Electro-Mechanical type relays manufactured by M/s English Electric Co. of India Ltd. (GEC-ALSTHOM) for 25kV traction sub-stations — a genuine, named real-world manufacturer, not a generic description.

Real Relay Type Designations & Ratings

DescriptionTypeRating/Setting Range
A) Transformer Percentage Biased DifferentialDDT-12Current setting 40-100% of 5A, 20%/30%/40% bias setting
IDMT overcurrent + instantaneous high-set overcurrent (132kV side)CDG-26 combined with CAC-13CDG: 16, 80-320% of 5A; CAG: 400-1600% of 5A
Restricted earth fault relay (132kV & 25kV side)CAG-1410-40% of 5A
IDMT overcurrent relay (25kV side)CDG-1680-320% of 5A
Aux relays for Buchholz, excessive winding & oil temp trippingVAA-33—
B) MHO-type directional distance protection relay (DPR)YCG-140.33 to 12 ohm extended zone each up to 60 ohm of 5A, MTA 75°
MHO relay for wrong phase coupling protection (WPC)YCG-140.33 to 12 ohm extended zone up to 60 ohm of 5A, MTA 125° with forward offset of 11%
Instantaneous high-set overcurrent relay, 25kV side (OC)CAG-17100-800% of 5A
C) Auxiliary relay for contact multiplication of YCG-14VAA-11—
Alarm bell relayVAA-21—
Flasher relayVAA-21—
Timer relay for single-shot auto-reclosingVAT-11—
🎯
Exam Focus — Same Type Number, Different Setting
A genuinely subtle real fact: BOTH the distance protection relay (DPR) AND the wrong-phase-coupling relay (WPC) use the exact SAME physical relay type — YCG-14 — with the SAME impedance range (0.33-12 ohm, extended zone up to 60 ohm). What differs is the MTA (Maximum Torque Angle) setting: 75° for standard distance protection, but 125° with an 11% forward offset for wrong-phase-coupling. This directly confirms and quantifies the earlier OHE Protection Scheme chapter's point that the WPC relay is an 'additional Mho relay' distinct from the standard one only by its torque angle setting — same hardware, different configuration.

D.C. Supervision — Auxiliary Relays (Type VAA-11)

A real 6-item list of DC supervision functions, ALL using the same VAA-11 relay type: Transformer HV CB trip supervision, Transformer LV CB trip supervision, 25kV Feeder control, 25kV Interruptor control, DC fail alarm cancel, and Alarm annunciation control.

Real Construction Requirements (Sections 5.5.3-5.5.9)

🎯
Exam Focus — Genuinely Precise, Real-World Numbers
This entire chapter is genuinely testable precisely because every figure is a REAL specification, not an illustrative example: 5A continuous current, 110V DC, 20% overload for exactly 8 hours, ±20% voltage tolerance, above 20VA burden. A real exam question could ask any one of these in isolation — e.g. 'what is the overload withstand duration for relay current coils?' with the answer being the specific 8-hour figure, not a rounded approximation.