Lead-acid batteries at traction substations/switching stations provide DC control supply, and demand real, precise maintenance discipline — a detailed history of every battery must be maintained, with fortnightly specific-gravity readings recorded.
Battery Room Safety
- Smoking, open flames, or spark-generating tools are STRICTLY FORBIDDEN in the battery room.
- The room must be well-ventilated, dust-free, with acid-proofing on walls and flooring, kept isolated from other electrical equipment, and given appropriate short-circuit fuse protection between the battery and distribution switchboard.
Specific Gravity — Real Numbers
- Variations in specific gravity between cells (from unequal evaporation) are corrected by adding DISTILLED WATER only — never concentrated/diluted sulphuric acid, except when acid is known to have spilled out.
- Hydrometer readings taken while a cell is gassing freely reflect a mixture of gas bubbles and electrolyte, NOT true electrolyte specific gravity — readings must be taken only after bubbles subside. Hydrometers should be 300mm length for required accuracy, and two should be kept per station, periodically cross-checked against each other.
Pilot Cells
One cell per row is selected as the 'pilot cell,' read frequently to indicate the state of charge/discharge as a guide to the condition of ALL other cells. Once selected, the pilot cell should NOT be changed unless it needs special treatment/repairs — and any such change must be noted immediately on record sheets. Its electrolyte height should invariably be kept at a fixed point (12mm above the top of plates), topped up with distilled water every fortnight if necessary.
Trickle Charging
Lead-acid batteries are sensitive to BOTH overcharging (positive plates shed active material quickly) and over-discharging (sulphation — whitish deposits on plates). There should be NO occasion for stationary traction installation batteries to sulphate, since terminal voltage of each cell is maintained close to 2.15V via a low, carefully-fixed trickle charge rate (milliamperes per Ah capacity).
Cell Voltage — Real Ranges
- New cells at end of full charge (10-hour rate): about 2.5 to 2.75V — this gradually decreases as the battery ages, settling to about 2.4V at normal temperature/charging rate.
- No cell should ever be discharged below 1.85V, as measured while discharging at the normal 10-hour rate.
Condition of Plates — Visual Diagnosis
In healthy cells in use for more than 12 months, when fully charged, the active material in positive plates should be CHOCOLATE in colour — a simple, real visual reference point for a healthy cell that a technician can check without special equipment. Sulphated plates, lug corrosion, and cracked separators all cause a noticeable terminal voltage drop when current flows, varying with the amount of current — hence the importance of comparing readings taken at consistent current levels.