Yearly Maintenance (PSI)

Electrical Engineering Traction Distribution Chapter 68/87 14 min read Source: Verified Source
हिन्दी में पढ़ें

Create a free account to track your reading, save important notes and practise this topic.

Yearly maintenance is the deepest, most instrumented level in the PSI maintenance hierarchy — moving from visual checks to laboratory-grade tests (dissolved gas analysis, capacitance/tan delta, precision resistance measurement).

General — Real, Specific Tasks

💡
Memory Aid — The Insect-Proofing Detail
A genuinely memorable, real instruction: open all trench covers, clean culverts, remove cobwebs, and specifically check the possibility of LIZARDS or other insects gaining entry into enclosed control equipment — making them insect-proof. This isn't a generic 'keep clean' instruction; it names a specific real-world failure mode (small animals entering control cabinets) that's easy to overlook.

Lightning Arresters

Bonding & Earthing — Annual Depth

🎯
Exam Focus — Testing Each Earth Electrode Group SEPARATELY
The real technique: check and record the resistance of EACH GROUP of earth electrodes AFTER DISCONNECTING IT from the common earth system — not measuring the whole combined system at once. This isolates any one weak electrode group that a combined-system reading would otherwise mask.

Traction Transformers — Annual Lab-Grade Tests

Isolators — Annual Precision Work

🎯
Exam Focus — The Ductor Test for Busbars
Busbar/connector contact resistance is measured using a 'Ductor' or other LOW-RESISTANCE measuring instrument — a genuinely different tool category from the monthly feel-by-hand check or the 500V/2500V Meggers used for insulation resistance elsewhere. This is precision contact-resistance measurement, not insulation testing.